We will send you an email to reset your password.
We will send you an email to reset your password.
Isolation relay (Gen 2) for Lifesaver smoke, heat and CO alarms for connection to auxiliary devices such as sirens, sounders, emergency lights, security and fire panels.
| Operating Coil Voltage |
5V – 10V DC |
|---|---|
| Secondary Contacts |
Normally Open |
| Contact options |
Pulse, Latching, CO Latching |
| Secondary Contact Rating |
240V AC 50Hz @ 5 Amps |
| Contact Switching Time Delay |
4 seconds once activated |
| Maximum No. of interconnected smoke alarms to a single LIFSAIR unit |
24 |
| Maximum number of LIFSAIR relay connected to one smoke alarm |
3 |
| Operating Temperature |
0° – 50°C |
| Dimensions |
89mm Deep x 68mm Wide x 45mm High |
Adding product to your cart