Isolation relay (Gen 2) for Lifesaver smoke, heat and CO alarms for connection to auxiliary devices such as sirens, sounders, emergency lights, security and fire panels. Relay is housed within a smoke alarm surface mounting block.
| Operating Coil Voltage |
5V – 10V DC |
|---|---|
| Secondary Contacts |
Normally Open |
| Contact options |
Pulse, Latching, CO Latching |
| Secondary Contact Rating |
240V AC 50Hz @ 5 Amps |
| Contact Switching Time Delay |
4 seconds once activated |
| Maximum No. of interconnected smoke alarms to a single LIFSAIR unit |
24 |
| Maximum number of LIFSAIR relay connected to one smoke alarm |
3 |
| Operating Temperature |
0° – 50°C |
| Dimensions |
125mm diameter x 24mm high |